RKI FP-300 Paper Tape Gas Monitor
High Sensitivity Toxic Gas Monitor
Features
- Small and compact
- Highly sensitive and ideal for low gas concentrations (ppb detection)
- Interference-free detection
- Easy detection tape replacement with plug-in cassette
- Tape remainder display and tape end warning alarm provided
- Easily transportable
Categories: Area Gas Detectors & Wireless Solutions, Gas and Flame Detection
Tags: gas detection, gas detector, gas monitor, gas sensor, toxic gas monitor
Brand RKI
Description
Datasheet [PDF]
Manual [PDF]
RKI’s paper tape monitors utilize highly sensitive colorimetric tapes to achieve interference free detection at low PPB and PPM levels Ammonia, Arsine, Chlorine, Diborane, Hydrogen Chloride, Hydrogen Fluoride, Hydrogen Sulfide, Phosphine, Silane. The FP-300 is equipped with an easily replaceable tape. This model is equipped with a digital display showing the type of gas and concentration in PPM or PPB. The FP-300 will also display remaining tape life as well as an end of tape alarm.
The FP-300 has audible and visual alarms, as well as alarm relay contacts and 4-20mA output. A unique “tape saver mode” extends tape life in applications where high background gas levels may be present.
The FP-300 meets and exceeds OSHA and NIOSH compliance requirements, and does not respond to interfering gases (hydrocarbons, alcohols, solvents, CO, etc.) that may be present in industrial/manufacturing environments. FP 330
Applications
- Scrubbers
- Environmental Monitoring
- Semiconductor Fabs
- Manufacturing
- Detecting uncaptured gas from scrubber
Specifications
| Model | FP-300 |
| Detection principle | Photoelectric photometry method using tape cassette |
| Detection tape | Plug in cassette |
| Detection range | see the table above |
| Accuracy | Within +/- 20% +1 of indication |
| Tape operation time | 1 month (with now alarm) Tape remainder display, Tape end warning |
| Alarm preset point | See the table above |
| Alarm functions | Latching (standard) or self reset. Lamp (Caution: Yellow, Warning: Red) and buzzer |
| Self-diagnosis | Sensor failure, low flow, tape failure, tape end warning, failure of tape setting, system error |
| External output signal | 4-20mA (300 Ω at maximum load resistance) |
| Operating temperature & humidity | 41-95°F (5~35°C) 30~90% RH (non condensing) |
| Power supply & power | 24VDC +/- 10% for panel mounting 100 VAC, 110 VAC, 117 VAC, 220 VAC for desktop |
| Dimensions & weight | Panel mounting: Approx. 6.5(W) x 6.5(H) x 10.3(D) Approx. 14.33lbDesktop: Approx. 6.5(W) x 7.8(H) x 10.4(D) Approx. 12.125lb |
Gases
| Gas | TLV | Detection Range | Resolution | 1st alarm | 2nd alarm | Tape No. |
| Amonia NH3 |
25ppm | 0.5~4ppm | 0.1ppm | 1ppm | 2ppm | FC-010 |
| Arsine AsH3 |
50ppb | 0~150ppb | 1ppb | 50ppb | 100ppb | FCL-001 |
| Chlorine Cl2 |
0.5ppm | *0~0.8ppm | 0.01ppm | 0.25ppm | 0.5ppm | FCL105 |
| 0~1.5ppm | ||||||
| Diborane B2H6 |
100ppb | 0~300ppb | 5ppb | 50ppb | 100ppb | FCL-002 |
| Hydrogen Chloride HCl |
5ppm | 0.25~1ppm | 0.025ppm | 0.5ppm | 0.75ppm | FC-004 |
| 1.5~8ppm | 0.1ppm | 2.5ppm | 5ppm | FC-005 | ||
| Hydrogen Fluoride HF |
3ppm | 0~9ppm | 0.1ppm | 1.5ppm | 3ppm | FC-006 |
| Hydrogen Sulfide H2S |
10ppm | 0~100ppm | 1ppb | 17ppb | 34ppb | FCL-001 |
| 0~10ppm | 0.05ppm | 1ppm | 2ppm | |||
| Phosphine PH3 |
300ppb | *0~500ppb | 5ppb | 150ppb | 300ppb | FCL-001 |
| 0~900ppb | ||||||
| Silane SiH4 |
5ppm | *0~8ppm | 0.1ppm | 2.5ppm | 5ppm | FCL-002 |
| 0~15ppm |